How to convert kVA to amps

Posted Sep 03, 2019

Converting kVA to amps sounds complicated to anybody unfamiliar with generator terminology, but it doesn’t have to be. Power Electrics has provided a step-by-step guide that’s designed to take you through converting kVA to amps with a simple formula.

To convert kVA to amps you will need to know the voltage of the circuit, then go ahead and use the formula shown below to calculate its power. Our generators run in three-phase circuits. To work this out we recommend using the following formula:

Example 1

Current (A) = (1,000 x Power (Gen size – kVA)) ÷ ( x Voltage (V))

(A) = (1,000 x kVA) ÷ (1.732 x V)

(A) = (1,000 x 75) ÷ (1.732 x 400)

(A) = 75,000 ÷ 693

(A) = 108

black-1072366
The example above (a three-phase formula) shows a generator with amps of 108 with a power of 75kVA. The kVA equates to the measure of the apparent power, but the kW is the actual power produced because KW= kVA x pf – check out our kW to kVA blog here for more info. Diesel generators typically have a power factor rating of 0.8, i.e. - pf (power factor) rating for Generators is 0.8.

Although a possibility, generators are seldom run at maximum load because it reduces the efficiency as well as the power rating of a generator. One kVA is equivalent to 1,000-volt amps. The electrical efficiency is typically expressed as a power factor between zero and one. The closer the power factor rating is to one, the more efficiently the kVA will be converted into kilowatts.

What Are Amps?

Amps are a measure of the electrical current running in a circuit. Put simply, electricity is the electrons that flow through a conductor – amps are the measure of how many electrons are flowing, also known as an electric current.

What Are Volts?

Volts – an abbreviation of voltage – are the force that moves electrons through a conductor. The higher the pressure, the more work the electrons can do. A useful comparison is water under pressure. The more pressure water is under, such as a pressure washer, the more efficiently it’s able to clean a stained floor or strip old paint from a wall. Similarly, moving electrons (current in amps) with pressure works most efficiently.

Did You Know?

The formula typically used in the “engineering world” is the following –

I = kW x 1000/x E x Power Factor

I = 60 x 1000/1.732 x 400 x 0.8

I = 60,000/554.24

I = 108

Whilst the working out provides the same answer as the initial example, the formula slightly differs. Rather than ‘A’ an ‘I’ is used to represent the amps, whilst the ‘E’ represents volts rather than a ‘V’.


« Back to blog

Like this story? Check out similar posts.

5 ways to make your generator quieter

When hiring or buying a generator, people often ask about noise levels. There’s a common idea that generators are noisy (and we refute that) but ...

CONTINUE READING

Generator sizing: a step by step guide

When it comes to generators, size matters. Undersize a generator and you won’t be able to power your equipment; oversize a generator and you’re wasting ...

CONTINUE READING

Your Guide To Generator Jargon

Alex Hill from the Power Electrics Hire team uses his experience to translate a range of frequently used generator terms into more easily understandable language... ...

CONTINUE READING

Four reasons why your generator fails to start

This blog will explore some of the common reasons why a diesel generator may fail to start and most importantly, how to reduce the risk ...

CONTINUE READING

Your Guide to The Medium Combustion Plant Directive (MCPD)

On November 25 2015 the European Parliament signed a new directive that regulates emission limits from medium combustion plants.

CONTINUE READING

Understanding your generator spec sheet

A standby generator could be an important asset to your business, but choosing the correct one for your requirements isn’t always the easiest thing to ...

CONTINUE READING

6 Generator Health & Safety Tips

Hiring a generator that provides sufficient temporary or standby power is one of the most important steps you will take in planning a successful project. ...

CONTINUE READING

Four Reasons to Consider a Hybrid Generator for your Next Project

Within this blog we explore how a hybrid generator could be incorporated into your next project along with the four key advantages.

CONTINUE READING

Your guide to the Non-Road Mobile Machinery (NRMM) legislation

This blog aims to inform you of the most important aspects of the NRMM legislation and how it can affect you.

CONTINUE READING

What is Black Start Testing

Black Start Testing is an important aspect of generator servicing, in this blog we look at what it is, where it originated and why it's ...

CONTINUE READING

What you need to know about Clean Air Zones

Clean Air Zones have begun to be introduced in cities across the UK, this blog explains the where, why, what and how.

CONTINUE READING

WANT TO DISCUSS YOUR PROJECT? PLEASE CALL +44 (0)370 850 0858

  • SOUTH WEST
  • LONDON
  • SOUTH WALES
  • MIDLANDS
  • SOUTH COAST

SOUTH WEST

GOOGLE MAP

LONDON

GOOGLE MAP

S.WALES

GOOGLE MAP

MIDLANDS

  • The Dell Business Park
  • Four Ashes
  • Wolverhampton
  • WV10 7DF
  • 01902 798898
GOOGLE MAP

SOUTH COAST

GOOGLE MAP